Powercom UPS Australia

Vanguard II 2000VA PSW On-Line, L Series *

$2,364.00 AUD inc. GST

On-Line Double Conversion, Industrial Pure Sine Wave (PSW), 0.9pf. Tower Style GPO Aus 3pin Outlets            
 LCD Front Panel, Network/Alarm Card Slot, External Battery Pack Connector and USB Interface.            

UPS
Model
VGS-2000-L
Capacity VA
2000
Capacity (Watts)
1800
Form
Tower
Phase
Single Phase
Energy Saving
Yes - ECO mode Efficiency > 94%
INPUT
Voltage
220 / 230 / 240 Vac
Voltage Range
120 ~ 276 Vac < 25% Load 140 ~ 276 Vac < 50% Load 160 ~ 276 Vac < 75% Load 180 ~ 276 Vac < 100% Load
Frequency Range
50 / 60Hz ±2.5Hz auto sensing (45 to 65Hz user selectable)
Power Factor
> 0.97
Cold Start
Yes
OUTPUT
Rated Power Factor
0.9
Waveform
Pure Sine Wave
Voltage
208 / 220 / 230 / 240 Vac ±2% (selectable output voltage)
Frequency
50 / 60 Hz ±0.25 Hz
Transfer Time
0 ms
Harmonic Distortion
< 5% of T.H.D. at non-Linear Load | < 2.5% of T.H.D. at Linear Load
Crest Factor
3 : 1
EPO Function
Yes
Efficiency
Approximately 89%
Connections
*Please refer below "Receptacle Options" Customized receptacle can be discussed
PROTECTION
Overload
Line Mode
106% - 120% for 30 seconds 121% - 150% for 10 seconds
Overload
Battery Mode
101% - 109% for 10 seconds 110% - 120% for 3 seconds
Tele-Communication
RJ45 x 2
Surge Protection
IEC 61000-4-5 Level 3
Bypass
Internal Bypass(Automatic and Manual)
Short Circuit Protection
UPS output cut off immediately or protected by input fuse or circuit breaker
Alarm
Buzzer beeps under backup mode, battery low, battery charging fault, and overload
Overload Protection
UPS automatic power off if overload exceeds 106% to 120% of nominal at 30 seconds; 121% to 150% for 10 seconds;
CHARGER
UPS
1A
UPS Build In
5A
Total
6A
BATTERY
Model
VGS-2000-L
DC Voltage
72V
MANAGEMENT
Indicator
LCD/LED Control Panel
Communication Port
RS232, USB(B-type)
SNMP Slot
Option
Audible Alarms
YES
PHYSICAL
Dimension (W×D×H)(mm)
225 x 420 x 358
Weight (kgs)
12.7
Shipping Dimensions (mm)
340 x 526 x 485
Shipping Weight (kgs)
15.5